*All Pictures shown are for illustration purposes only. Actual product may vary due to enhancement*
8 - 10 Week Lead Time
1-year/1000 hours Warranty with Free parts and service guidance!
Master industrial generator sets are fully integrated power generation systems that provide optimum performance, dependability, and versatility for standby and prime power applications.
Pictures are of an actual unit sold to a customer in May 2022
Technical specifications
Model |
ST-C550GF |
Hz |
60 Hz |
Power factor |
0.8 P.F |
Standby |
600 kW |
Prime Power |
550 kW |
Key Specifications |
Powered by a top-tier engine, alternator, and control panel |
Relay Brand |
Top-of-the-line Siemens APT |
Micro Brand |
LS |
Wire Pipes |
PA Corrugated pipes |
Battery Brand |
Camel-DF |
Voltages |
110 / 220 V (Single Phase), 208 V (Three Phase), 240 / 480 V (Three Phase), 575 V (Three Phase), 600 V (Three Phase) |
Prime power
This rating is for continuous electrical power supply (at variable load). There is no limit on the annual hours of operation, and 10% overload power can be supplied for 1 hour in 12.
Standby power
This rating is for the supply of continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted.
Features
- Every generator set is subjected to a comprehensive test program which includes 50% load, 75% load, 100% load, 110% load and the checking and proving of all control and safety shut-down functions
- 24V DC start motor
- Equipped 24V high performance maintenance-free lead-acid starting batteries and connecting with cables
- Equipped with industrial silencer and flexible exhaust hose
- Designed to Comply with ISO8528/GB2820
- Powered by Cummins engine, Stamford alternator, and SmartGen control panel
Cummins Engine Technical Data
Model |
QSK19-G5 |
Manufacturer |
Cummins |
Number of Cylinders |
6 Cylinders inline |
Cycle |
4 Stroke |
Aspiration |
Turbocharged |
Bore x Stroke (mm x mm) |
159 x 159 |
Displacement |
19 L |
Compression Ratio |
14.5:1 |
Prime Power with Fan / Speed |
608 kW/1800rpm |
Standby Power with Fan / Speed |
669 kW/1800rpm |
Speed Governor |
ECM |
Cooling System |
Forced water cooling cycle |
Steady Speed Drop |
≤1% |
Total Lubrication System Capacity |
84 L |
Fuel Consumption at 75% Load |
120 L/h |
Starter Motor |
DC24V |
Alternator |
DC24V |
Stamford Alternator Technical Data
Alternator Model |
HCI544E CSA Approved |
Max Power |
550 kW |
Frequency/Speed |
60Hz/1800rpm |
Exciter Type |
Single Bearing, Brushless, Self-excited |
Power Factor |
0.8 |
Voltage Adjust Range |
≥5% |
Voltage Regulation NL-FL |
≤+1% |
Insulation Grade |
H |
Protection Grade |
IP23 |
Phase |
3 |
SmartGen Control Panel Technical Data
Model: HGM6110CAN
The control module gives digital readouts of
- Generator voltage
- Output frequency
- Engine speed
- Battery voltage
- Engine hours run
The control module has indicators for failure information
- Overspeed/Underspeed
- Emergency stop
- Low oil pressure
- High water temperature
- Failure to start
- Battery charger failure
Automatic shutdown occurs under
- Low engine oil pressure
- High engine water temperature
- Overspeed/Underspeed
- Failure to start after three attempts
Options/Add-Ons Available
For more details, call or text: +1 (647) 363-5872