*All Pictures shown are for illustration purposes only. Actual product may vary due to enhancement*
8 - 10 Week Lead Time
1-year/1000 hours Warranty with Free parts and service guidance!
Master industrial generator sets are fully integrated power generation systems that provide optimum performance, dependability, and versatility for standby and prime power applications.
Powered by Volvo engine, Stamford alternator, and SmartGen control panel
Prime power
This rating is for continuous electrical power supply (at variable load). There is no limit on the annual hours of operation, and 10% overload power can be supplied for 1 hour in 12.
Standby power
This rating is for the supply of continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted.
Features
- Every generator set is subjected to a comprehensive test program which includes 50% load, 75% load, 100% load, 110% load and the checking and proving of all control and safety shut-down functions
- 24V DC start motor
- Equipped 24V high-performance maintenance-free lead-acid starting batteries
- Equipped with industrial silencer and flexible exhaust hose
- Designed to Comply with ISO8528/GB2820
Volvo Engine Technical Data
Model |
TAD753GE |
Manufacturer |
Volvo Penta |
Number of Cylinders |
6 Cylinders, Vertical Inline |
Cycle |
4 Stroke |
Aspiration |
Wastegate Turbocharger |
Bore x Stroke (mm x mm) |
108 x 130 |
Displacement |
7.15 L |
Compression Ratio |
18:1 |
Prime Power with Fan / Speed |
192 kW/1800rpm |
Standby Power with Fan / Speed |
213 kW/1800rpm |
Speed Governor |
ECM |
Cooling System |
Forced Liquid Cooling Cycle |
Steady Speed Drop |
≤1% |
Total Lubrication System Capacity |
34 L |
Fuel Consumption at 100% Load |
217 g/kW h |
Starter Motor |
DC24V |
Alternator |
DC24V |
Stamford Alternator Technical Data
Alternator Model |
UCI274G CSA Approved |
Max Power |
183 kW |
Frequency/Speed |
60Hz/1800rpm |
Exciter Type |
Single Bearing, Brushless, Self-excited |
Power Factor |
0.8 |
Voltage Adjust Range |
≥5% |
Voltage Regulation NL-FL |
≤+1% |
Insulation Grade |
H |
Protection Grade |
IP23 |
Phase |
3 |
SmartGen Control Panel Technical Data
Model: HGM6110CAN
The control module gives digital readouts of
- Generator voltage
- Output frequency
- Engine speed
- Battery voltage
- Engine hours run
The control module has indicators for failure information
- Overspeed/Underspeed
- Emergency stop
- Low oil pressure
- High water temperature
- Failure to start
- Battery charger failure
Automatic shutdown occurs under
- Low engine oil pressure
- High engine water temperature
- Overspeed/Underspeed
- Failure to start after three attempts
Options/Add-Ons Available