down image
400 kW Prime Power Diesel Generator (Volvo Engine) (600/347V Three Phase 60Hz) (EPA/CARB Tier 4F)
400 kW Prime Power Diesel Generator (Volvo Engine) (600/347V Three Phase 60Hz) (EPA/CARB Tier 4F)
  • Load image into Gallery viewer, 400 kW Prime Power Diesel Generator (Volvo Engine) (600/347V Three Phase 60Hz) (EPA/CARB Tier 4F)
  • Load image into Gallery viewer, 400 kW Prime Power Diesel Generator (Volvo Engine) (600/347V Three Phase 60Hz) (EPA/CARB Tier 4F)

400 kW Prime Power Diesel Generator (Volvo Engine) (600/347V Three Phase 60Hz) (EPA/CARB Tier 4F)

Regular price
£130,211.00
Sale price
£130,211.00
Regular price
£134,157.00
Sold out
Unit price
per 
Shipping calculated at checkout.

*All Pictures shown are for illustration purposes only. Actual product may vary due to enhancement*

12 - 16 Week Lead Time

1-year/1000 hours Warranty with Free parts and service guidance!

Master industrial generator sets are fully integrated power generation systems that provide optimum performance, dependability, and versatility for standby power, prime power and continuous power applications. 

Powered by Volvo Engine, Stamford Alternator, and Deepsea Control Panel

Included Features 

  • Technologically advanced Remote Wifi Controller 
  • Next-Generation Brushless Stamford CSA Approved Alternator 
  • Inbuilt Webasto Style Coolant Heater to prevent cold starts and increase the engine's longevity 
  • Silent Soundproof Weather Protection Canopy/Enclosure 
  • Standard 8 Hour Dual Wall Base Fuel Tank 
  • Electronic Speed Governor

Prime power 

This rating is for continuous electrical power supply (at variable load). There is no limit on the annual hours of operation, and 10% overload power can be supplied for 1 hour in 12. 

Standby power 

This rating is for the supply of continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted. 

Features 

  • Every generator set is subjected to a comprehensive test program which includes 50% load, 75% load, 100% load, 110% load and the checking and proving of all control and safety shut-down functions
  • 24V DC start motor
  • Equipped 24V high-performance maintenance-free lead-acid starting batteries
  • Equipped with industrial silencer and flexible exhaust hose
  • Designed to Comply with ISO8528/GB2820, NEC, CEC 

Volvo Engine Technical Data

Model 

TAD1672VE

Manufacturer 

Volvo

Number of Cylinders 

6 Cylinders Inline

Cycle 

4 Stroke 

Aspiration 

Turbocharged & Charge Air-Cooled

Bore x Stroke (mm x mm) 

144 x 165

Displacement 

16.12 L 

Compression Ratio 

16.5:1 

Prime Power with Fan / Speed 

465 kW/1800rpm 

Standby Power with Fan / Speed 

515 kW/1800rpm 

Speed Governor 

ECM 

Cooling System 

Forced Liquid Cooling Cycle 

Steady Speed Drop 

≤1% 

Total Lubrication System Capacity 

48 L 

Coolant capacity

45 L

Fuel Consumption at 100% Load

201 g/kW.h

Starter Motor

DC24V

Alternator

DC24V

Stamford Alternator Technical Data 

Alternator Model 

HCI544

CSA Approved 

Power 

400 kW 

Frequency/Speed 

60Hz/1800rpm 

Exciter Type 

Single Bearing, Brushless, Self-excited 

Power Factor 

0.8

Voltage Adjust Range 

≥5% 

Voltage Regulation NL-FL 

≤+1% 

Insulation Grade 

Protection Grade 

IP23 

Phase 

3

Deepsea Control Panel Technical Data 

Model
DSE

The control module gives digital readouts of (Including but not limited to):
  • Generator voltage
  • Output frequency
  • Engine speed
  • Battery voltage
  • Engine hours run

The control module has indicators for the following failure information (Including but not limited to): 
  • Overspeed/underspeed
  • Emergency stop
  • Low oil pressure
  • High water temperature
  • Failure to start 
  • Battery charger failure

Automatic shutdown occurs under (Including but not limited to):
  • Low engine oil pressure
  • High engine water temperature
  • Overspeed/underspeed
  • Failure to start after three attempts

Options/Add-Ons Available 

For more details, call or text: +1 (647) 363-5872

master-aire.myshopify.com