down image
60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
  • Load image into Gallery viewer, 60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
  • Load image into Gallery viewer, 60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
  • Load image into Gallery viewer, 60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
  • Load image into Gallery viewer, 60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
  • Load image into Gallery viewer, 60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)
  • Load image into Gallery viewer, 60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)

60 kW Prime Power Cummins Diesel Generator (480/277V Three Phase 60Hz)

Regular price
$27,999.99
Sale price
$27,999.99
Regular price
$32,000.00
Sold out
Unit price
per 
Shipping calculated at checkout.

*All Pictures shown are for illustration purposes only. Actual product may vary due to enhancement*

8 - 10 Week Lead Time 

1-year/1000 hours Warranty with Free parts and service guidance!

Master industrial generator sets are fully integrated power generation systems that provide optimum performance, dependability, and versatility for standby and prime power applications. 

Powered by Cummins Diesel Engine, Stamford CSA Approved Alternator and SmartGen Control Panel 

Included Features 

  • Technologically advanced Remote Wifi Controller 
  • Next-Generation Brushless Stamford CSA Approved Alternator 
  • Inbuilt Coolant Heater to prevent cold starts and increase the engine's longevity. 
  • Silent Soundproof Weather Protection Canopy/Enclosure 
  • Base Fuel Tank 
  • Electronic Speed Governor

 

Battery Brand: Camel battery  

Relay Brand: Siemens APT 

Micro Brand: LS 

Wire Pipes: PA Corrugated pipes 

Prime power 

This rating is for continuous electrical power supply (at variable load). There is no limit on the annual hours of operation, and 10% overload power can be supplied for 1 hour in 12. 

Standby power 

This rating is for the supply of continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted. 

Features 

  • Every generator set is subjected to a comprehensive test program which includes 50% load, 75% load, 100% load, 110% load and the checking and proving of all control and safety shut-down functions 
  • Equipped with a 24V DC start motor & 24V high-performance maintenance-free lead-acid starting batteries  
  • Equipped with industrial silencer and flexible exhaust hose 
  • Designed to Comply with ISO8528/GB2820 

Cummins Engine Technical Data

 

Model 

4BTA3.9-G2

Manufacturer 

Cummins 

Number of Cylinders 

4 Cylinders, Vertical inline

Cycle 

4 Stroke 

Aspiration 

Turbocharged & Aftercooled

Bore x Stroke (mm x mm) 

102 x 120 

Displacement 

3.9L 

Compression Ratio 

17.3:1 

Prime power/Speed 

67kW/1800rpm

Standby Power/Speed 

74kW/1800rpm

Speed Governor 

Electrical

Cooling System 

Forced Liquid Cooling Cycle 

Steady Speed Drop 

≤1% 

Total Lubrication System Capacity 

10.9L 

Coolant Capacity 

8.3L 

Fuel Consumption at 100% Load

214g/kW h

Starter Motor 

DC24V 

Alternator 

DC24V 

Stamford Alternator Technical Data 

Alternator Model 

UCI224F CSA Approved 

Max Power 

60 kW 

Frequency/Speed 

60Hz/1800rpm 

Exciter Type 

Single Bearing, Brushless, Self-excited 

Power Factor 

0.8

Voltage Adjust Range 

≥5% 

Voltage Regulation NL-FL 

≤+1% 

Insulation Grade 

H 

Protection Grade 

IP23 

Phase 

3

SmartGen Control Panel Technical Data 

ModelHGM6110 

The control module gives digital readouts of 

  • Generator voltage 
  • Output frequency 
  • Engine speed 
  • Battery voltage 
  • Engine hours run 

The control module has indicators for failure information 

  • Overspeed/Underspeed 
  • Emergency stop  
  • Low oil pressure 
  • High water temperature 
  • Failure to start  
  • Battery charger failure 

Automatic shutdown occurs under 

  • Low engine oil pressure  
  • High engine water temperature  
  • Overspeed/Underspeed 
  • Failure to start after three attempts 